Thermal Insulation

R-Values of Common Plumbing Piping and Insulation.

In certain areas, AS3500 requires a minimum insulation of R=0.3, no current piping material will meet this requirement without suitable thermal insulation.

"R-value = Thickness / Conductivity. See AS3500.4 Section 8.6"

Conductivity (k)W/m/K
OD mm
ID  mm
Wall thickness mm
R-Value K.m²/W
Air
0.02
6
0.3
Copper DN15
401
12.7
10.88
0.91
0.0000023
Lagged Copper (Approx..)
Cu + Air + Plastic
~2
0.034
Sharkbite PE-X 16mm
0.35
16
11.6
2.2
0.006
Sharkbite PE-X 20mm
0.35
20
15.1
2.45
0.007
Sharkbite PE-X 25mm
0.35
25
18.6
3.2
0.009
E-Thermâ„¢
0.034
8
0.235
Requirement of AS3500.1 5.19 DN15
0.03
9
0.3
Requirement of AS3500.4 2003
amendment 1 2005 (table 8.1 & 8.2)
0.0433
13
0.3