Fire Rating

Wall Penetration

(tested on 2-hour rated plasterboard wall - Report #2253500)

Pipe

16mm PE-X
20mm PE-X
25mm PE-X

Fire Protection

Promat CFC32
Promat CFC32
Promat CFC32

Fire Rating

-/180/180
-/180/180
-/180/180

Floor Penetration

(tested on 120mm Concrete Slab - Report #2253500)

Pipe

16mm PE-X
20mm PE-X
25mm PE-X

Fire Protection

Promat CFC32
Promat CFC32
Promat CFC32

Fire Rating

-/180/90
-/180/180
-/180/120

Fire Rating is in the form x/y/z, where x,y and z are minutes of rating to each of the following: Structural adequacy/Integrity/Insulation

a "-" means the test is not applicable

Normal specification for Pipe penetrations is -/120/120, anything bigger than this is adequate