Fire Rating
Wall Penetration
(tested on 2-hour rated plasterboard wall - Report #2253500)
Pipe
16mm PE-X
20mm PE-X
25mm PE-X
|
Fire Protection
Promat CFC32
Promat CFC32
Promat CFC32
|
Fire Rating
-/180/180
-/180/180
-/180/180
|
Floor Penetration
(tested on 120mm Concrete Slab - Report #2253500)
|
Pipe
16mm PE-X
20mm PE-X
25mm PE-X |
Fire Protection
Promat CFC32
Promat CFC32
Promat CFC32 |
Fire Rating
-/180/90
-/180/180
-/180/120 |
Fire Rating is in the form x/y/z, where x,y and z are minutes of rating to each of the following: Structural adequacy/Integrity/Insulation
a "-" means the test is not applicable
Normal specification for Pipe penetrations is -/120/120, anything bigger than this is adequate

|